Voltage
Regulators: |
|
|
|
|
|
|
|
AC Power
Supplies: |
|
- Potency: from 3 to 1000 KVA:
-Single phase: from 3 to 200 KVA.
-Three phases: from 10 to 1000 KVA.
- Voltages: 110V, 115V, 120V, 127V, 220V, 230V, 380V, 440V, 460V, 480V and
others to order.
- Frequency : 60Hz and 50Hz + or - 5%.
- Input estabilization: + ou - 20%.
- Maximun output voltage variation : + ou - 1%.
- Estabilization coeficient ( input/output ) : 20.
- Do not introduce harmonic distortion.
- Time of total recuperation : 16,6ms - optional : 8,3ms
- Eficiency : Superior to 98%.
- Consumption in empty: Less than 0,2%.
- Power factor of the estabilizator: Bigger than 0,98.
- Eletronic Control System : By INTEL and MICROCHIP
last generation microcontrollers - 33Mhz and 20Mhz
with 68 pinos.
- Voltage monitor in TrueRMS value: Independent on the
wave form, temperature variation from 0 to 60 ºC
and frequency from 40 to 80 Hz.
- Regulation System: Indirect - by induction on the
line by the "Buck-boost" transformer.
- Quantity of regulation curvs: 32 "tap changer"
in linear form.
Obs.:There is a special model with 64 "tap changer"
duplicanting the coeficient of estabilization.
- Regulation process: Totally static and independent
in each phase.
- Over and under tension protection + missing phase:
with programation of limits and times.
- Dotated with event memorization or event log: Exibit
current and last events.
- RS 232 serial comunication for monitor and event
log purposes.
- Soft start: When turning on, it rises up the voltage
until the objective point in a gradative way.
- Do not turn on the output if the tension is not
normal.
- Automatic recharge: Programmed in number of times
and time for recharge.
- The same can be desactivated depending on the client
needs. In this last case the charge enhancement is
manual.
- By-Pass return tries: Programable in numbers of
times and time. It can be habilitated or not. Once
in protection mode, if the voltage come back to normal
like programmed.
- Recharge tries by protection: After in protection
mode if tension comes back to normal it returns to
normal operation like programmed.
- Event warnings: Sonorous, illuminant and messages
on the display.
- Board connections: Everything with quick connection.
- Control panel and command:
- Built in alfa-numeric keyboard with
16 buttons.
- Liquid cristal 4 lines display with 20 characters
per line with backlight.
- Mechanic estabilizator's on/off switch in the built
in keyboard.
- Mechanic charge's on/off switch with light indicator.
- Simultaneous exibit of 4 or more parameters and/or log events.
- Isolation with eletrostatic armour-plating (optional).
- Termomagnetic disjunctor in the input for protection
against overload.
- Eletromagnetic contactor for output comutation and
desarm in protection cases.
- Automatic and independent By-Pass
on each phase with programable limits and times.
- Reduced dimensions.
- Programable output tension: + or - 10%.
- Acceptable overload: 10% during 1h: 100% during
15 Min and 500% during 1Sec
.
Obs.: This uppercharges for protection efects are programable
up to 6 scales respectivelly in its percentuals and
its times.
- Liquid cristal display with 4 lines with 20 characters
per line with the exibit's fuctions:
- Simultaneous visualization of the 3
output tension of each phase ralating with the neuter
( R/N, S/N and T/N ).
- Simultaneous visualization of the 3 output tension
of each phase ralating with the other ( R/S, R/T and
S/T ).
- Simultaneous visualization of the 3 input tension
of each phase relating to the neuter ( R/N, S/N and T/N
).
- Simultaneous visualization of the 3 input tension
of each phase relating to the other ( R/S, R/T and S/T
).
- Simultaneous vizualization of the output tension,
input tension, frequency and of the regulation mark
of R's phase.
- Simultaneous vizualization of the output tension,
input tension, frequency and of the regulation mark
of S's phase.
- Simultaneous vizualization of the output tension,
input tension, frequency and of the regulation mark
of T's phase.
- Simultaneous vizualization of the 3 actual corrent
in phases R, S and T.
- Simultaneous vizualization of the potency, serial
number, fabrication date and model of the estabilizator.
- A menu that informs how to make the the by-pass manual,
the return of the by-pass, turn on the charge, turn
off the charge, enter in the ajust parameters by using
a password and return to the normal mode.
- Reset to the stardards configurations.
- Occurred event and messages visualization. Ex.: Active
By-Pass - phase S / lowertension / Reactivated.
Obs.:You can see this functions on the PANEL
simulation session of the site by clicking on the alfa-numeric
buttons. (Panel in Portuguese).
|